ECE 558 - Spring 2021
Power System Reliability
Project 7 - Due 20 Apr 2021
- Two systems are interconnected by two 16 MW tie lines. System A
has four 30 MW generating units with forced outage rates of 10%.
System B has eight 15 MW generating units with forced outage rates of
8%. For each system, calculate the loss of load expectation in days
and the expected load curtailed in MW for a one-day period, given that the
peak load in both System A and System B is 100 MW and the tie lines
are 100% available.
- Repeat the analysis for the above problem, assuming that the tie
lines have failure rates of 5 failures/year and average repair times of
24 hours.